What is the PUE of the Strasbourg Datacenter ? Print

  • 2

Calculation of energy savings based on the PUE value

StandarddatadockSaved
PUE 1.62 1.21 25%
Overhead 62% 21% 66%

Calculation of power saving on the basis of kWh at full load

Maximum capacity datadock 8,000 kW
Active power with PUE 1.21 6,612 1.21
Overhead with PUE 1.21 1,388 kW
Overhead with PUE 1.62 4,313 kW
Saving datadock 2,925 kW
Annual saving datadock 25,623,000 kWh
CO2 per kWh¹ 0.935 kg
Saving datadock 23,957,505 kg
CO2 absorption tree/year² 200 kg
Capacity 119,788 trees

¹ Source: PSI, IER; average 935 g CO2 per kWh power from black coal

² Source: United Nation Framework for Climate Change Convention (UNFCCC), average value for carbon offset of trees